Kane 455 CPA1 Flue Gas Analyser Kit (KANE455CPA1KIT)
BUYKane 455 CPA1 Flue Gas Analyser Kit (KANE455CPA1KIT)
Features
- Long Life CO Sensor (>5 years expected life)
- Long Life IR based CO2 sensor (>5 years expected life)
- Low Annual Service Costs
- Easy to use rotary switch
- Protective rubber sleeve with magnet for "hands free" use
- Multi-fuel:
- Natural Gas
- Propane
- Butane
- LPG
- Light Oils (28/35 sec)
- Wood Pellets
- High accuracy manometer
- Differential thermometer
- Built-in LED torch
- Separate reports for:
- Combustion Pressure
- Let-by and Tightness
- Temperature
- CO build up
- Designed to meet BS7967
- Easy transfer of test results
- 5 years extended warranty if serviced annually by KANE
Included Accessories
- Appliance sampling probe kit
- 12V in-vehicle charger
- Reference DVD
- Plug-in gas leak detector
- Air / liquid temperature probe
- 2 x Pipe clamp probes
- Soft protective carry case
- Infra-red printer
- Flue Probe
- Protective rubber sleeve with integral magnet
- 2 x Pressure connectors
- 4 x AA NiMh batteries with fast charger
- Instruction manual
Optional Accessories
- Range of probes for air, liquid and surface temperatures
- Bluetooth wireless module (factory fitted)
- XML compatible data output for Service Managament software programs (such as Cognito)
| Instrument Specifications | |
|---|---|
| Operating Temperature Range | 0° to 45°C |
| 10% to 90% RH non-condensing | |
| Atmospheric pressure: 850 to 1100mbar | |
| Battery | 4 AA Cells. > 8 hours using Alkaline AA cells |
| Chargers (optional) | 220V charger for NiMH batteries only |
| 12V in-vehicle charger for NiMH batteries only | |
| Preprogrammed Fuels | Natural Gas, LPG, Light Oil(28.35 sec), Propane, Butane, Wood pellets |
| Display | Backlit LCD |
| Torch | Inbuilt LED torch |
| Data Storage | 99 Combustion tests |
| 20 Pressure tests | |
| 20 Tightness tests | |
| 20 Temperature tests | |
| 20 Room CO tests | |
| Time & Date | 24 Hour Real Time Clock |
| Dimensions | 200mm x 90mm x 45mm |
| Weight | 0.8kg |
| Conforms to | BS7927 |
| Resolution | Accuracy | Range | |
|---|---|---|---|
| Temperature Measurement | |||
| Flue Temperature | 0.1°C/F | ± 1.5°C | 0 - 600°C |
| ± 1% reading | 0 - 1200°C with special probe | ||
| Inlet Temperature | |||
| Internal Sensor | 0.1°C/F | ± 1°C | 0 - 50°C |
| External Sensor | 0.1°C/F | ± 1.5°C | 0 - 6000°C |
| ± 1% reading | |||
| Gas Measurement | |||
| Oxygen ** | 0.3% | ± 0.2% * | 0-21% |
| Carbon Monoxide | 1ppm | ± 5ppm<100ppm * | 0-2,000ppm norm |
| ± 5% of reading >100ppm | 4,000ppm max for 15 minutes | ||
| Carbon Dioxide | 0.1% | ± 0.2% reading* | 0-20% |
| Calculated Values *** | |||
| Efficiency | 0.1% | 0-99.9% | |
| Excess Air | 0.1% | 0-250% | |
| CO/CO2 Ratio * | 0.0001 | 0-0.9999 | |
| Pressure (differential) | |||
| Nominal range ± 80 mbar (Maximum over range without damage to sensor is ± 400 mbar) |
0.001 mbar to 24.999 bar then 0.01 mbar |
± 0.005 mbar ± 0.03 mbar ± 3% of reading |
± 0.2 mbar ± 1 mbar ± 80 mbar |
| Resolution | Accuracy | Range | |
* Derived from CO2 measurement, ** Derived from O2 measurement, *** All calculations in accordance with BS EN50379 approval

























Click to Zoom